Tandem Central Compressor Unit (Midium Temp)

  • Tandem Central Compressor Unit (Midium Temp) Manufacturers, Tandem Central Compressor Unit (Midium Temp) Factory, Supply Tandem Central Compressor Unit (Midium Temp)
Tandem Central Compressor Unit (Midium Temp)
  • Bingshan
  • China
  • 60-90days
  • 3000 set/year

Scope
Medium Type Tandem Central Compressor Units(60HP~120HP)118.11kw~256.22kw
Application
Multi-compressor parallel unit is widely applied in supermarket, logistic center etc. medium and low temp cold storage.

Tandem Central Compressor Unit (Midium Temp)


Features

 

1. Large Capacity Range. Long Running Life

2. Adopt reasonable energy-saving stage 4~6 and similar power compressor to keep good energy-saving effect and 15years design running life.

3. Reliable Oil Level Control

4. Large capacity oil tank and purely mechanical oil level float valve control system ensure compressor head oil return effectively and reliability.

5. Complete Security Design

6. Adopt double loop circuit to ensure system avoid from losing. Any components failure will not affect another loop normal work.

7. To ensure partial failure does not affect the unit running, the unit is added maintenance valve on the refrigerant loop. Add partial RCCB on the circuit to ensure 1/2`~2/3 capacity as the failure is happened.

 

Medium Temp Tandem Central Compressor Units Technology Parameter Table


Type

Refrigerant

Nominal Condition

Evap. Temp. Range

Cond. Temp. Range

Compressor

Noise

Outline

Net Weight

Ref. Cap.

Input Power

Type

Displacement/unit

Cooling Method

Length

Width

Height



kw

Kw


m3/h


dBA

mm

mm

mm

kg

LCU-601MPJ

R22

118.11

57.78

—20~—5

20~57


73.5×3


69.4

2365

1130

1763

1600

Four-compressor Parallel

Liquid Injection Cooling

LCU-701MPJ

R22

132.06

67.41

—20~—5

20~57


39.5*1,73.5*3


69.4

2365

1130

1763

1650

Four-compressor Parallel

Liquid Injection Cooling

LCU-801MPJ

R22

145.08

75.97

—20~—5

20~57


73.5×4


69

2365

1130

1763

1700

Four-compressor Parallel

Liquid Injection Cooling

LCU-901MPJ

R22

167.4

86.67

—20~—5

20~57


39.5*1,73.5×4


70.4

2915

1130

1763

1990

Five-compressor Parallel

Liquid Injection Cooling

LCU-1001MPJ

R22

181.35

95.23

—20~—5

20~57


73.5×5


69.9

2915

1130

1763

2045

Five-compressor Parallel

Liquid Injection Cooling

LCU-1101MPJ

R22

203.67

104.86

—20~—5

20~57


39.5*1,73.5×,5


69.9

4013

1046

1895

2405

Six-compressor Parallel

Liquid Injection Cooling

LCU-1201MPJ

R22

216.69

113.42

—20~—5

20~57


73.5×6


69.9

4013

1046

1895

2460

Six-compressor Parallel

Liquid Injection Cooling

LCU-N601MPJ

R22

133.64

62.39

—20~—5

20~57


45.4*2,73.5×2


74.2

2365

1130

1763

1600

Four-compressor Parallel

Liquid Injection Cooling















LCU-N701MPJ

R22

152.19

71.11

—20~—5

20~57

Four-compressor Parallel

45.4*1.73.5×3

Liquid Injection Cooling

74.2

2365

1130

1763

1650

LCU-N801MPJ

R22

170.82

79.67

—20~—5

20~57


73.5×4


73

2365

1130

1763

1700

Four-compressor Parallel

Liquid Injection Cooling

LCU-N901MPJ

R22

195

91.05

—20~—5

20~57


45.4*1,73.5×4


74.4

2915

1130

1763

1990

Five-compressor Parallel

Liquid Injection Cooling

LCU-N1001MPJ

R22

213.52

98.78

—20~—5

20~57


73.5×5


74

2915

1130

1763

2045

Five-compressor Parallel

Liquid Injection Cooling

LCU-N1101MPJ

R22

237.66

110.83

—20~—5

20~57


45.4*4,73.5×5


74

4013

1046

1895

2405

Six-compressor Parallel

Liquid Injection Cooling

LCU-N1201MPJ

R22

256.22

119.14

—20~—5

20~57


73.5×6


74

4013

1046

1895

2460

Six-compressor Parallel

Liquid Injection Cooling

 

Note

1. Ref. Cap, input power and displacement test condition (nominal condition): Evap. Temp: -6.7℃, Cond. Temp: 48.9℃, Suction Temp.: 18.3℃,  Ambient Temp: 35℃

2. Noise value is tested in front of unit within 1m x 1m at high condensing pressure. The actual noise value could be different as per actual condition.

3. LCU-601MPJ~LCU-1001MPJ have upgrade type. Additional mount differential oil pressure alarm and receiver low level alarm.