HomeFAQ

FAQ

  • Abnormal vibration

    Foundation bolt unsecured
    Screw the foundation bolt
    1.Compressor is not coaxial with motor
      Secondary alignment
    2.Unit vibration because of piping vibration 
      Increase support points or change the support.
    3.Excess liquid refrigerant suction into the unit
      Adjust refrigerant supply, turn down the suction stop valve.
    4.Slide valve can't locate and vibrate.
      Check whether the oil piston and valves leak or not
    5.Suction chamber high vacuum
      Turn up the suction stop valve
    Unfold
  • Discharge temperature or oil temperature is too high

    1.Compression ratio is too large
    Reduce discharge pressure and load
    2.Oil temperature is too high
    Clean the oil cooler, reduce water temperature or increase water flow 
    3.Superheated steam inhalation
    Liquid supply to evaporation system
    4.Oil injection quantity not enough
    Increase oil injection quantity
    5.Air enter into the refrigeration system
    Exhaust air and check the spare parts
    Unfold
  • Inadequate refrigeration capacity

    1.Slide valve position is not right or other fault
    Check the indicator, adjust slide valve position, and maintain the slide valve
    2.Suction filter blocked
    Remove the filter and clean the filter screen
    3.Abnormal machine wearing out contribute to excessive gap  
    Adjust or change parts
    4.Suction piping resistance loss is too large
    Check valves (like suction stop valve, check valve)
    5.Leak between high and low system
    Check by-pass piping
    6.Oil injection quantity not enough, cannot seal
    Check oil system
    7.Discharge pressure much higher than condensing pressure
    Check discharge system piping and valves and reduce the pressure
    8.Suction stop valve not open entirely
    Open the suction valve
    Unfold
  • Large start load or cannot start

    1.Slide valve not stops to 0
      Adjust slide valve to 0
    2.Screw compressor inside is filled with lubricating oil or liquid refrigerant
      Rotate the compressor along the operation direction to drain the effusion or remained oil.
    3.Some moving components serious wear or burn
      Maintain and replace the spare parts
    4.Under voltage
      Check the power grid voltage value